Garage Heater Size Calculator
Posted by MN Garage Notes Editorial Team Published
This calculator estimates the heat a garage loses on a cold design day, in BTU per hour and watts. It adds up each surface's area divided by its R-value, adds the heat lost to outside air leaking in (1.1 BTU/h per cfm per degree, with cfm = air changes per hour x volume / 60), multiplies by the indoor-to-outdoor temperature difference and adds a labelled 10 to 20 percent allowance. It is a planning estimate: the heater's manual, its rating plate and a licensed professional decide what you install, and no fuel-burning heater is safe without the venting, fresh air and clearances its manual requires.
Garage heater size calculator
Enter your garage. The estimate updates as you type and your inputs are saved in the page address so you can bookmark or share it. Nothing leaves your browser. Sizes are in feet and temperatures in degrees Fahrenheit.
How the garage heater size calculator works
The calculator estimates the steady heat loss of the garage at one cold design condition. Each surface (walls, door, ceiling, optionally floor) loses heat in proportion to its area divided by its R-value. Outside air leaking in must also be warmed. Both are multiplied by the temperature difference. A separate, labelled allowance is added at the end, so you can see the pure calculation and the margin apart.
Q (BTU/h) = [ sum( A ÷ R ) + 1.1 × V × ACH ÷ 60 ] × ΔT required output = Q × (1 + allowance) watts = required output ÷ 3.412 amps = watts ÷ volts branch circuit (fixed electric heater) = amps × 1.25 fuel input (BTU/h) = required output ÷ heater efficiency
- A
- surface area in square feet (walls net of the door)
- R
- R-value of that surface in h·ft²·°F/BTU
- V
- garage volume in cubic feet
- ACH
- air changes per hour
- 1.1 ÷ 60
- BTU/h per cubic foot per air change per degree F (0.0183, the familiar 0.018)
- ΔT
- indoor target minus outdoor design temperature, °F
Worked example
Given: 24 x 24 ft garage, 9 ft ceiling, 16 x 7 ft door at R-6; walls R-15, ceiling R-30, floor not counted; indoor 50 °F, outdoor -8 °F (ΔT = 58 °F); 1 air change per hour, 15 percent allowance, 240 V electric.
- Surfaces:
Walls (net of door) 752 ft² ÷ R-15 = 50.1; Overhead door 112 ft² ÷ R-6 = 18.7; Ceiling 576 ft² ÷ R-30 = 19.2 (BTU/h per °F); total 88 - Air leakage:
1.1 × 5,184 ft³ × 1 ÷ 60 = 95 BTU/h per °F - Heat loss:
(88 + 95) × 58 = 10,616 BTU/h - With the 15 percent allowance:
10,616 × 1.15 = 12,209 BTU/h = 3,578 W - Electric at 240 V:
3,578 W ÷ 240 = 14.9 A, and 14.9 × 1.25 = 18.6 A for the branch-circuit sizing
Answer: About 12,209 BTU/h (3,578 W) of heat output on that design day. Leakage is about 52 percent of the loss in this example, so sealing the door and walls matters as much as adding R-value.
Constants and where they come from
| Constant | Value | Source |
|---|---|---|
| Sensible heat of air | 1.1 BTU/h per cfm per °F | Source 1 |
| Air leakage presets | tight 0.5, average 1, leaky 1.5 ACH (residential) | Source 2 |
| Example outdoor design temperature | -8 °F (Hennepin County, 99% heating) | Source 3 |
| Air films and layer R-values | outside 0.17, inside 0.68, plywood 0.62, gypsum 0.45 | Source 4 |
| Watts to BTU/h | 3.412 | Sources 5 to 7 |
| Fixed electric heating branch circuit | 125% of the load | Source 8 |
| Electric ratings in the "nearest rating" line | 5,000 W, 7,500 W, 10,000 W: ratings printed in the manuals above, not a catalogue of what is sold | Sources 5 to 7 |
Each constant is stored with its source, link and date in the site's data files.
Planning assumptions (not sourced facts)
These defaults only fill the drop-downs. Replace them with the R-value of your own door label or construction using the override boxes.
| Choice | R used | Basis |
|---|---|---|
| Uninsulated wall or ceiling | 1.92 | Sum of sourced layers: 0.17 + 0.62 + 0.45 + 0.68 (empty cavity air space ignored) |
| Partly insulated wall / ceiling | 8 / 11 | Planning assumption |
| Well insulated wall / ceiling | 15 / 30 | Planning assumption |
| Bare door panel | 0.85 | Sourced air films only |
| Thin / thick insulated door | 3 / 6 | Planning assumption: use the R printed on your door |
| Allowance | 10 to 20% | Planning margin, user input |
Assumptions and limits
- It is a steady-state, single-condition estimate. It ignores wind, solar gain, a cold concrete slab, thermal bridging through framing, stored heat in the building and the time to warm up from a cold start.
- The air-leakage presets are residential-house figures from the 1983 BNL report. A garage with an overhead door and no air sealing can leak more: use the override if you know your ACH.
- R-values you type are used as entered. Framing lowers the real R of a wall or ceiling, so a whole-assembly R is lower than the insulation's labelled R.
- The result is heat output needed. It is not a recommendation of any model, brand or fuel, and it does not replace the manufacturer's sizing or a load calculation by a licensed professional.
- "Nearest rating" lists only the electric ratings printed in the manuals we opened. For fuel-burning heaters compare the shown input BTU/h with the rating plate, and check the manual's rules on venting, fresh air and garage installation.
- The 125 percent branch-circuit line is for fixed (hard-wired) electric heaters under the NEC text cited. Cord-and-plug heaters, local amendments and other editions differ. An electrician sizes the circuit.
Next: lower the load first with the garage insulation R-value calculator, and read how to heat a garage.
Frequently asked questions
How many BTUs do I need to heat my garage?
It depends on the garage size, how well it is insulated, how leaky it is and how much warmer you want it than the outside design temperature. Enter those into the calculator. The answer is a heat-loss estimate in BTU per hour at one design condition, not a guarantee of comfort on the coldest night.
Is the answer the size of heater to buy?
No. It is the heat the garage is estimated to lose, so it is the heat output a heater needs to replace. Compare it with the output rating in the manual of any specific heater, and follow that manual for installation. Fuel-burning heaters are labelled by input BTU/h, which is higher than output; the calculator shows the input for the efficiency you enter.
What is the difference between BTU input and output?
Input is the fuel energy per hour a gas or propane heater burns. Output is the heat it delivers, input times its efficiency. Take the efficiency from the heater's rating plate or manual. Electric resistance heaters convert all their electricity into heat, so their watts convert directly to BTU/h.
Why does the calculator add a 10 to 20 percent allowance?
The simple steady-state method ignores wind, the frozen floor, thermal bridging through framing, door gaps and a cold start. The allowance is a labelled planning margin, not a sourced value. The result shows the figure with your chosen allowance and the 10 and 20 percent bounds.
Is it safe to use a propane or kerosene heater in a closed garage?
This tool cannot tell you that. Fuel-burning heaters produce carbon monoxide, and an unvented heater needs the ventilation, clearances and CO alarms its manual specifies. Read the heater safety guide, follow the manual and ask a licensed professional about gas, venting and permits.
What outdoor temperature should I use?
The default (-8 F) is a 99 percent design value for Hennepin County: it is warmer than that 1 percent of the hours. A colder number gives a bigger load. If you want the heater to keep up on rare cold nights, enter a colder temperature.
Does it count heat lost through the concrete floor?
By default, no. A slab loses heat to the ground in a way this simple formula does not model. You can count the floor at the full temperature difference, which overstates the loss, as a cautious upper case.
Sources and further reading
- Brookhaven National Laboratory BNL-66610, J.W. Andrews, "How to Heat and Cool a Home with 400 CFM Supply Air" (U.S. DOE, 1999): sensible load = 1.1 x cfm x temperature difference (osti.gov) Opened 2026-11-17.
- Brookhaven National Laboratory BNL 51698, G. Dennehy (U.S. DOE, 1983): infiltration about 1 ACH average, 1/2 ACH tight, 1 1/2 ACH leaky (osti.gov) Opened 2026-11-17. Residential figures.
- ENERGY STAR Certified Homes Design Temperature Limit Reference Guide (2015 Edition), Exhibit 1: Hennepin County, MN 99% heating -8 F (energystar.gov) Opened 2026-11-17.
- Building Science Corporation / DOE Building America, Guide to Insulating Sheathing (rev. Jan 2007): air films 0.17 and 0.68, 1/2 in plywood 0.62, 1/2 in gypsum 0.45 (www1.eere.energy.gov) Opened 2026-11-17.
- Dyna-Glo EG10000DH instruction manual: 10,000 W / 240 V / 34,120 BTU (printed rating, cited for the conversion only) (cdn.shopify.com) Opened 2026-11-17.
- Dyna-Glo EG7500DGP instruction manual: 7,500 W / 240 V / 25,590 BTU (cdn.shopify.com) Opened 2026-11-17.
- Marley Engineered Products FUH Series unit heater manual (5200-11195-000): 5,000 W / 240 V / 17,065 BTU/h (marleymep.com) Opened 2026-11-17.
- NFPA 70 (NEC) 2020 text as reproduced in the 2022 California Electrical Code, 424.4(B) Branch-Circuit Sizing: not smaller than 125 percent of the load (law.resource.org) Opened 2026-11-17. Check the edition your jurisdiction has adopted.
- CPSC, Carbon Monoxide Information Center (cpsc.gov) Opened 2026-11-17.
- CDC, About Carbon Monoxide Poisoning (cdc.gov) Opened 2026-11-17.